Warehouse emergency lighting: integrated or standalone?
When you upgrade warehouse lighting you also need a clear plan for emergency lighting: what the law requires, when to put a pack in a fitting, and when a standalone luminaire or exit sign is the better choice.
Standalone options include the PS-BULKHEAD IP65 bulkhead (including emergency versions), the PS-HELP twin-spot emergency luminaire, and PS-EXIT LED exit signs.
The short answer
Escape routes and exits that need illumination must have emergency lighting if the normal supply fails, and routes must be signed (Regulatory Reform (Fire Safety) Order 2005). You do not usually need a battery in every high bay. Design the escape routes, open areas and any high-risk task areas, then choose integrated packs, standalone luminaires and exit signs to match. Polaris supplies integrated options, standalone emergency luminaires and exit signs, and UKEX-certified ATEX emergency lighting for hazardous zones.
What the law and the standards require
- RRO 2005 (England and Wales), article 14: emergency routes and exits that need illumination must have emergency lighting of adequate intensity if normal lighting fails, and must be indicated by signs.
- HM Government fire safety risk assessment guide for factories and warehouses: larger or complex premises are likely to need a more comprehensive automatic emergency escape lighting system; test systems monthly and have annual testing and maintenance by a competent person.
- BS 5266-1:2025 is the UK code of practice for emergency lighting design (published October 2025, replacing the 2016 edition).
- BS EN 1838:2024 sets emergency lighting performance requirements, including escape route and open area illuminance.
- BS EN 50172:2024 (BS 5266-8:2024) covers the safety of emergency escape lighting systems, including documentation and automatic test systems.
Under BS EN 1838:2024, escape routes need at least 1 lx horizontal at floor level (with edge borders excluded by route width), and open (anti-panic) areas need at least 0.5 lx where the risk assessment requires them. Duration and whether 1 hour or 3 hours applies depend on the risk assessment and BS 5266-1; many UK schemes use a 3-hour rated duration. Verify the design against the current standards for your site.
Integrated emergency
An emergency pack inside a batten, panel or high bay keeps the same optic and mounting. It suits corridors, stores and lower areas where the normal fitting already covers the escape route. Limits include battery size, ambient temperature and how many points you really need on a high warehouse floor.
PS-BATTEN 60-S EM combines the built-in microwave sensor with a 3-hour emergency version. PS-PANEL and PS-PANEL+ can take an emergency pack accessory. PS-UFO-MAX is available with an emergency option.
Standalone luminaires and exit signs
Standalone emergency luminaires and exit signs mark routes and cover points that the normal high bay layout does not serve well, such as changes of direction, fire equipment and final exits. Polaris supplies standalone emergency luminaires and exit signs. Ask us to include them in the design when you upgrade the main lighting.
Why not every high bay needs a battery
At 10 to 15 m, a battery in every UFO high bay is often the wrong answer. A lighting design to BS 5266-1 and BS EN 1838 places emergency light where people escape and gather, which may be a smaller set of integrated fittings plus standalone points and signs. Stand-by dimming on occupancy sensors is not emergency lighting; see warehouse lighting sensors.
Cold stores
Battery performance falls in the cold. Check operating temperature for any emergency option and use fittings rated for the space. The free cold store lighting guide covers temperature, IP and sensors for chillers and freezers.
ATEX and hazardous zones
Polaris supplies UKEX-certified ATEX emergency lighting for hazardous areas. We also supply and install in hazardous zones with our own team. Start with the ATEX lighting overview and the free ATEX lighting guide. No certificate numbers are published on this site.
When to review emergency lighting in an LED upgrade
Changing layout, lux levels or fitting positions can change escape lighting. Our LED high bay installation process considers emergency lighting against BS 5266-1 where it is affected. The warehouse LED lighting upgrade guide includes a compliance and funding checklist.
Frequently asked questions
Does every high bay need an emergency battery?
Usually no. Escape routes, open areas and high-risk task areas are designed to BS 5266-1 and BS EN 1838. Many schemes use a mix of integrated packs in battens or panels and standalone emergency luminaires or exit signs, rather than a battery in every high bay.
What is integrated vs standalone emergency lighting?
Integrated means an emergency pack in the same fitting that provides the normal light (for example a batten or panel). Standalone means a dedicated emergency luminaire or exit sign. Polaris supplies both, plus ATEX emergency lighting for hazardous zones.
Does PS-BATTEN have an emergency version?
Yes. PS-BATTEN 60-S EM combines the built-in microwave sensor with a 3-hour emergency version.
What standards apply to warehouse emergency lighting?
In England and Wales the Regulatory Reform (Fire Safety) Order 2005 sets the legal duty. Design and testing commonly follow BS 5266-1:2025, BS EN 1838:2024 and BS EN 50172:2024. The HM Government factories and warehouses fire safety guide covers larger premises.
Is ATEX emergency lighting available?
Yes. Polaris supplies UKEX-certified ATEX emergency lighting for hazardous areas, as well as standalone emergency luminaires and exit signs. Ask us for the right fitting for your zones; see ATEX lighting.